High-Speed PVC Roll-Up Door (Rapid Roll Door / Cleanroom High-Speed Door)
Product Overview
Features & Specifications
Detailed Description
High-speed roll-up door specifications: opening and closing speed, curtain and drive
Open fast, close steadily: opening speed is 0.8–1.5 m/s, and closing slows to 0.5–0.8 m/s to reduce the risk of hitting people or vehicles. The drive is a 0.75–1.5 kW servo motor, which can be installed on single-phase 220 V.| Item | BS-RD-S cleanroom type | BS-RD-C industrial type |
|---|---|---|
| Door frame | SUS304 | Painted steel |
| Opening speed | 0.8–1.5 m/s | 0.8–1.5 m/s |
| Closing speed | 0.5–0.8 m/s | 0.5–0.8 m/s |
| Curtain | 0.8–1.2 mm PVC-coated polyester fabric | 0.8–1.2 mm PVC-coated polyester fabric |
| Drive | Servo motor 0.75–1.5 kW | Servo motor 0.75–1.5 kW |
| Suitable for | Cleanrooms, biotech, food clean areas | Logistics openings, warehouses, general factories |
Why use a high-speed roll-up door in a cleanroom?
A cleanroom must stay at positive pressure relative to the outside, and the longer and wider a door is open, the more clean air escapes. A high-speed roll-up door opens fast and closes automatically after passage, so it is open for much less time than a manual door; a strip curtain always has gaps.| Comparison | High-speed roll-up door | Strip curtain | Manual door |
|---|---|---|---|
| Sealing at rest | Fully sealed when closed | Gaps between strips | Sealed when properly closed |
| Passage | Opens and closes automatically, hands-free | Walk straight through | Opened and closed by hand, often left open |
| Pressure maintenance | Good | Poor | Depends on user habits |
| Suitable for | Logistics openings with frequent people and vehicle traffic | Separation between areas of the same class | Rooms with infrequent traffic |
High-speed door safety and activation: photocells, safety airbag, radar and interlock
The door must not close while a person or vehicle is underneath; this is the most important safety requirement for a high-speed door. Infrared photocells and a bottom safety airbag are standard: if the photocell beam is interrupted the door does not close, and if the airbag touches a person or object the door reverses upward immediately. The European standard EN 12453 covers the safety in use of this kind of power-operated door.| Activation | Method | Suitable for |
|---|---|---|
| Push button / pull cord | Triggered manually by personnel | Occasional pedestrian traffic |
| Radar | Opens automatically when people or vehicles approach | Frequent people and vehicle traffic |
| Induction loop | Sensed when a forklift or vehicle drives over | Logistics openings |
| Access control / interlock | Card access, or interlocked with an air shower or a second door | Cleanroom entrances, double-door buffer zones |
High-speed door wind resistance, airtightness and power failure
Aluminium alloy wind bars are fitted across the curtain at intervals, more for wider doors, so the curtain does not bulge and leave its guides outdoors or where there is a pressure difference; wind resistance is classified by EN 12424 (Class 1 is 300 Pa, Class 2 is 450 Pa) and air permeability by EN 12426. In a power failure the door can be wound open with a manual crank, and a UPS can be added where the door must keep operating during outages.| Item | Method |
|---|---|
| Wind resistance | Aluminium alloy wind bars, arranged by door width and pressure difference |
| Side sealing | Brushes or seals in the guide rails to reduce air leakage |
| Knocked out of the guides | Optional zipper-guided curtain re-engages automatically on the next cycle |
| Power failure | Opened with a manual crank; UPS optional |
| Maintenance | Regularly check photocells, safety airbag and curtain wear |
Frequently Asked Questions
How long does a high-speed roll-up door take to open and close?
Opening speed is 0.8–1.5 m/s, so a 3 m high door opens fully in about 2–4 seconds; closing speed is 0.5–0.8 m/s, about 4–6 seconds to close fully. The automatic closing delay after people or vehicles pass is adjustable; at busy logistics openings it can be shortened to reduce the time the door stays open.
Can a high-speed roll-up door hit people or vehicles?
Two safety devices are standard: when the infrared photocells on both sides of the frame are interrupted, the door will not close; and as soon as the bottom safety airbag touches a person, a vehicle or an object on the floor, the door reverses upward immediately. An infrared light curtain can also be added to detect across the full height of the doorway.
What is the difference between the cleanroom type and the industrial type?
The cleanroom type BS-RD-S has a SUS304 door frame and roller box that withstand wiping and disinfection, do not rust and do not shed paint, suited to cleanrooms, biotech and food clean areas; the industrial type BS-RD-C has a painted steel frame at lower cost, suited to logistics openings, warehouses and general factories. Both have the same opening and closing speeds and drive.
Selection References
Before ordering, verify the efficiency grade, media type, and whether the operating environment fits your requirements.