LT-Type Air Shower - Cleanroom Equipment | Baisheng Tech
Product ID:air-shower-lt-typeCleanroom EquipmentCleanroom Equipment
Cleanroom Equipment

LT-Type Air Shower

Product Overview

The LT-type air shower has its doors on walls facing different directions: the L type has two doors at 90°, and the T type has three doors and serves as an anteroom shared by two areas. A straight-through air shower requires the entrance and exit to be in a straight line, whereas the LT type allows the air shower to be placed at a corridor corner, or separates the entry and exit routes. The basic principles of showering and interlocking are the same as for the straight-through type; the difference is the number and position of the doors: a wall occupied by a door cannot carry nozzles, so the nozzles are placed on the remaining walls and the ceiling; the interlock of three doors must ensure that only one is open at any time. A typical single-person enclosure measures approx. 1200–1300 × 1000–1500 × 2100–2180 mm externally, with actual dimensions custom-made to suit the floor layout.

Features & Specifications

►Types: L type (two doors at 90°) / T type (three doors, shared anteroom) ►Nozzle arrangement: on the walls without doors and the ceiling; the number depends on door positions and enclosure depth ►Nozzle air velocity: approx. 20–25 m/s ►External dimensions: single-person approx. 1200–1300 × 1000–1500 × 2100–2180 mm (W × D × H) ►Internal dimensions: width approx. 800 mm, height approx. 1960–1980 mm, depth according to the enclosure ►Filtration: G4 pre-filter + H13 HEPA (H14 optional) ►Shower time: 0–99 s, adjustable ►Door interlock: electronic interlock; only one door open at any time ►Power supply: three-phase 380 V or single-phase 220 V, 50 Hz ►Specification note: the above are typical configurations; dimensions, number of nozzles, door type and materials are custom-made to suit the site

Detailed Description

The difference between the L and T types

The L type has two doors on two adjacent walls at an angle of 90°. The most common use is at a corner: where a corridor ends and turns towards the cleanroom, a straight-through unit will not fit, and the L type takes up exactly that turn. The T type has three doors, making the air shower an anteroom shared by three directions. A typical configuration has one door to the outside and two doors leading to two different clean areas; or one entrance, one exit and one door to the changing area. It lets one air shower serve two areas, saving one unit and a length of corridor.
ConfigurationThe three doors lead toPurpose
One entrance, two areasOutside corridor, clean area A, clean area BTwo adjacent clean areas share one entrance
Separate entry and exitChanging area (in), clean area, exit corridor (out)People entering and people leaving do not cross at the same door
Changing room connectionOutside corridor, changing area, clean areaThe air shower also serves as a buffer before and after the changing area

Why separate the entry and exit routes

Using the same door for both entering and leaving means that people about to enter cross paths in the same space with people who have just left, carrying process particles or chemical residues. In a small cleanroom with only a few people going in and out this can be handled by scheduling; with many people, or where the process raises cross-contamination concerns, physically separating the routes is more reliable. This is consistent with the emphasis of EU GMP Annex 1 (2022) on the gowning procedure and airlocks (§7.10, §4.12): reducing contamination relies on process design, and the door positions of the air shower are a tool for putting that process into the floor plan.

Interlock logic for three doors

The T-type interlock is not "two doors never open at the same time" but "only one of the three doors is open at any time". In addition, define in advance which door may open after the shower ends: people coming in from outside can only open towards the clean area, and people coming out of the clean area can only open towards the outside. Whether showering is needed in the direction leaving the clean area can be set as required, for example interlock only without showering, to shorten the wait when leaving. Whether the door locks stay locked or are released during a power failure must be decided together with the fire escape routes and written into the operating procedure.

Where to make up the nozzles on walls taken by doors

In the straight-through type both side walls are complete, so nozzles can be distributed symmetrically over them; in the L and T types one or two side walls are taken up by doors, and that side has no nozzles. A common approach is to add nozzles on the other side and the ceiling, or to increase the enclosure depth and fit more nozzles on the wall sections outside the doors. Even so, shower coverage is still not as good as the symmetrical straight-through type, so it is more important for people to turn around during the shower; floor markings inside the enclosure can guide standing position and turning.

Key points for site measurement

The LT type depends more on the site floor plan than the straight-through type: the swing direction of each door (push in or out, left- or right-hand), the thickness and material of the walls on both sides of the corner, differences in floor level, and whether there is enough swing clearance outside the doors must all be confirmed before drawings are issued. If all three doors of a T type are swing doors, their swing ranges in three directions must not interfere with each other. It is recommended to draw on the floor plan the opening range of each door and the standing and turning positions of people during the shower, to confirm that open door leaves do not block nozzles and that people's standing positions are not within the swing range of a door leaf.
How do I choose between an L-type and a straight-through air shower?

It depends on whether the entrance and exit are in a straight line. Use the L type, with two doors at 90°, where the corridor turns in front of the cleanroom and a straight-through unit will not fit. The trade-off is that one side wall is occupied by a door and that side has no nozzles; nozzles must be added on the other side and the ceiling, coverage is not as good as the symmetrical straight-through type, and people need to turn around during the shower. A typical single-person enclosure measures approx. 1200–1300 × 1000–1500 × 2100–2180 mm externally.

Can two of the three T-type doors be open at the same time?

No. The T-type interlock allows only one of the three doors to be open at any time; otherwise the air shower loses its airlock function, and the two clean areas, or a clean area and the outside, would be directly connected. When ordering, it is also necessary to define which door may open after the shower ends (determined by the direction of entry), and whether the door locks stay locked or are released during a power failure, to be confirmed together with the fire escape routes.

Is showering needed when leaving the cleanroom?

Not necessarily. The purpose of the shower is to reduce particles brought into the clean area, so it is usually not needed in the leaving direction and can be set to interlock only, without showering, to shorten the wait when leaving; but the interlock should be kept so that both doors are not open at the same time on the way out. The LT type can separate the entry and exit doors so that the settings for the two directions are independent of each other.

Selection References

Before ordering, verify the efficiency grade, media type, and whether the operating environment fits your requirements.