HEATMOS H14CU/H13CU EN-Standard HEPA Filter (350°C) - NIPPON MUKI | Baisheng Tech
Product IDNM-H14CUNIPPON MUKIHeat-Resistant HEPA
NIPPON MUKI

HEATMOS H14CU/H13CU EN-Standard HEPA Filter (350°C)

Product Overview

H14CU/H13CU is an EN 1822-compliant heat-resistant HEPA filter for continuous operation at 350°C (peak 400°C × 1h), available in H13 and H14 efficiency grades (@ MPPS). Its mini-pleats construction supports scan testing, making it the preferred leak-free filter for pharmaceutical depyrogenation tunnels. Key features ・Continuous operation up to 350°C, peak 400°C × 1h ・EN 1822 H13 / H14 compliant (@ MPPS) ・Mini-pleats: high airflow, low pressure drop ・Leak-free, scan-testable ・H13: 99.95% / H14: 99.995% Target industries:Pharmaceutical

Features & Specifications

No.ModelEfficiencyW (mm)H (mm)D (mm)Airflow (CMM)Airflow (CMH)Initial PD (Pa)
1H14CU-Z-Q-FS4CS99.995%@MPPS(H14)30561015011.0660270
2H14CU-Z-Q-FS4CS99.995%@MPPS(H14)45745715012.5750270
3H14CU-Z-Q-FS4CS99.995%@MPPS(H14)76245715022.01320270
4H14CU-Z-Q-FS4CS99.995%@MPPS(H14)45761015017.51050270
5H14CU-24-Q-FS4CS99.995%@MPPS(H14)61061015024.01440270
6H14CU-Z-Q-FS4CS99.995%@MPPS(H14)76261015030.51830270
7H14CU-Z-P-FS4CS99.995%@MPPS(H14)30561029216.5990270
8H14CU-Z-P-FS4CS99.995%@MPPS(H14)45761029225.51530270
9H14CU-35-P-FS4CS99.995%@MPPS(H14)61061029235.02100270
10H14CU-Z-P-FS4CS99.995%@MPPS(H14)76261029244.02640270
11H13CU-Z-Q-FS4CS99.95%@MPPS(H13)30561015011.0660250
12H13CU-Z-Q-FS4CS99.95%@MPPS(H13)45745715022.01320250
13H13CU-Z-Q-FS4CS99.95%@MPPS(H13)45761015017.51050250
14H13CU-24-Q-FS4CS99.95%@MPPS(H13)61061015024.01440250
15H13CU-Z-Q-FS4CS99.95%@MPPS(H13)76261015030.51830250
16H13CU-Z-P-FS4CS99.95%@MPPS(H13)30561029216.5990250
17H13CU-Z-P-FS4CS99.95%@MPPS(H13)45761029225.51530250
18H13CU-35-P-FS4CS99.95%@MPPS(H13)61061029235.02100250
19H13CU-Z-P-FS4CS99.95%@MPPS(H13)76261029244.02640250

Email:sales@baisheng-tech.com

Phone+886-2-25981958

Detailed Description

HEATMOS is Nippon Muki’s EN-standard HEPA range developed for GMP-regulated pharmaceutical environments. The mini-pleats construction increases airflow per face area by 30-50% versus separator-type filters while lowering pressure drop. Scan-testable to satisfy GMP Annex 1.

Materials & Construction

PropertySpecification
Filter frameSTAINLESS STEEL
MediaGLASS PAPER
Max. temperature350°C (Max. 400°C/1h)
SeparatorSTAINLESS STEEL
GasketGLASS PAPER
Grille (downstream)-
Grille (upstream)-
SealantGLASS FIBER + CERAMIC
Max airflowCan be calculated on request
Max final PD (Pa)500

Airflow vs Pressure Drop (representative)

0100200300400500010002000300040005000Air volume (m³/h)Pressure drop (Pa)H13CU 150mm (Q)H13CU 290mm (P)
Representative H13 curves shown. H14 has slightly higher initial PD (~+20 Pa) at the same size.

Applications

- Depyrogenation tunnels in pharmaceutical manufacturing - High-temperature zones of aseptic filling lines - Biopharmaceutical high-temperature processing

Selection Notes

- **H13 (99.95%)** — meets EU GMP general clean zone requirements. - **H14 (99.995%)** — meets ISO Class 5 or stricter. - **150 mm (Q) / 290 mm (P)** — choose by airflow demand and installation depth.

Selection References

Before ordering, verify the efficiency grade, media type, and whether the operating environment fits your requirements.