PureChemix G ACGM/ACGL Recirculation Air Activated Carbon Filter - NIPPON MUKI | Baisheng Tech
Product IDNM-ACGMNIPPON MUKIActivated Carbon Chemical Filters
NIPPON MUKI

PureChemix G ACGM/ACGL Recirculation Air Activated Carbon Filter

Product Overview

ACGM/ACGL is a granular activated-carbon chemical filter, ~90% efficiency. ACGL (mini-pleats) has ultra-low PD (15-40 Pa) for recirculated air; ACGM (separator type) offers high airflow for large chemical-filtration duties. Targets alkaline gases (NH3) and organic VOCs. Key features ・Granular activated-carbon media ・Two forms: ACGL (mini-pleats) and ACGM (separator) ・Removes alkaline NH3 and organic VOCs ・Long life in recirculated-air systems Target industries:Electronics

Features & Specifications

No.ModelEfficiencyW (mm)H (mm)D (mm)Airflow (CMM)Airflow (CMH)Initial PD (Pa)
1ACGL-Z-R-E-*1Approx. 90%*2289594503.0180Approx. 15
2ACGL-10-R-E-*1Approx. 90%*26106105010.0600Approx. 15
3ACGL-20-R-E-*1Approx. 90%*212206105020.01200Approx. 15
4ACGL-Z-RS-E-*1Approx. 90%*2289594654.0240Approx. 30
5ACGL-10-RS-E-*1Approx. 90%*26106106510.0600Approx. 30
6ACGL-20-RS-E-*1Approx. 90%*212206106520.01200Approx. 30
7ACGL-Z-S-E-*1Approx. 90%*2289594754.0240Approx. 40
8ACGL-7-S-E-*1Approx. 90%*2610610757.0420Approx. 40
9ACGL-14-S-E-*1Approx. 90%*212206107514.0840Approx. 40
10ACGM-56H-E42-*1Approx. 90%*230561029028.01680Approx. 98
11ACGM-56-E42-*1Approx. 90%*261061029056.03360Approx. 98
12ACGM-Z-E42-*1Approx. 90%*276061029070.54230Approx. 98

Email:sales@baisheng-tech.com

Phone+886-2-25981958

Detailed Description

The PureChemix G range uses activated carbon as the primary absorbent, targeting the alkaline AMCs (NH3) and organic contaminants that matter most in semiconductor fabs. ACGL mini-pleats plugs directly into FFU slots; ACGM separator handles high-flow duty.

Materials & Construction

PropertyACGLACGM
Filter frameALUMINUMALUMINUM
MediaGranular activated carbonGranular activated carbon
Max. temperature40°C40°C
Relative humidity90%RH90%RH
SeparatorHOT MELT ADHESIVEALUMINUM
GasketEPDMEPDM
SealantPOLYURETHANE RESINPOLYURETHANE RESIN
Max airflowCan be calculated on requestCan be calculated on request

Airflow vs Pressure Drop (representative)

050100150200010002000300040005000Air volume (m³/h)Pressure drop (Pa)ACGL 50mmACGL 65mmACGL 75mmACGM 290mm
Four representative curves (3 ACGL depths + ACGM 290 mm). ACGL PD is far lower than ACGM.

Applications

- NH3 control in semiconductor fabs - VOC absorption in recirculated air - AMC control around EUV / DUV equipment

Selection Notes

- Recirculated air + low PD → ACGL (mini-pleats). - High-airflow outside-air treatment → ACGM (separator). - For acidic gases, choose ECSL.

Selection References

Before ordering, verify the efficiency grade, media type, and whether the operating environment fits your requirements.