CKR Heat-Resistant Pre-Filter (450°C) - NIPPON MUKI | Baisheng Tech
Product IDNM-CKRNIPPON MUKIHeat-Resistant HEPA
NIPPON MUKI

CKR Heat-Resistant Pre-Filter (450°C)

Product Overview

CKR is an ultra-heat-resistant pre-filter rated for continuous 450°C service, primarily used in automotive paint-booth and combustion-exhaust applications. Heat-resistant non-woven media captures coarse particulates such as paint overspray, carbon particles and ash. Key features ・Continuous operation up to 450°C ・Effective coarse particulate capture ・Designed for paint booths and combustion exhaust ・Non-woven media, easy replacement Target industries:Building, Medical, Food, Pharmaceutical, Electronics, Power generation, Nuclear power

Features & Specifications

No.ModelEfficiencyW (mm)H (mm)D (mm)Face velocity (m/s)Initial PD (Pa)
1CKR08045%@0.4μm(44%@0.4μm)500500252.5(1.5)196(98)
2CKR04043.5%@0.4μm(53%@0.4μm)500500252.5(1.5)343(196)
5CKR08045%@0.4μm(44%@0.4μm)500500502.5(1.5)343(157)
6CKR04043.5%@0.4μm(53%@0.4μm)500500502.5(1.5)627(314)

Email:sales@baisheng-tech.com

Phone+886-2-25981958

Detailed Description

CKR is Nippon Muki’s high-temperature pre-filter for automotive paint-booth ovens, protecting downstream HEPAs from heavy paint-overspray or carbon-particle loading. The 450°C rating also suits post-combustion exhaust pre-treatment.

Materials & Construction

PropertySpecification
Filter frameGALVANIZED STEEL / STAINLESS STEEL
MediaGLASS FIBER
Max. temperature450°C
Separator-
Gasket-
Grille (downstream)GALVANIZED STEEL / STAINLESS STEEL
Grille (upstream)GALVANIZED STEEL / STAINLESS STEEL
Sealant-
Max airflowCan be calculated on request
Max final PD (Pa)D=25mm: CKR080 392Pa(2.5m/s)/196Pa(1.5m/s), CKR040 686Pa(2.5m/s)/392Pa(1.5m/s); D=50mm: CKR080 686Pa(2.5m/s)/314Pa(1.5m/s), CKR040 392Pa(2.5m/s)/1254Pa(1.5m/s)

Applications

- Automotive paint-booth drying ovens - Coarse filtration on combustion exhaust - Air handling near boilers in power plants

Selection Notes

- Specified by face velocity (m/s), not volumetric CMH. - Service life is short due to high dust load — pair with differential-pressure monitoring. - Always install a downstream heat-resistant HEPA (ATMWC / ATMCU).

Selection References

Before ordering, verify the efficiency grade, media type, and whether the operating environment fits your requirements.