H14CH/H13CH EN-Standard HEPA Filter (250°C) - NIPPON MUKI | Baisheng Tech
Product IDNM-H14CHNIPPON MUKIHeat-Resistant HEPA
NIPPON MUKI

H14CH/H13CH EN-Standard HEPA Filter (250°C)

Product Overview

H14CH/H13CH is an EN 1822-compliant 250°C heat-resistant HEPA filter, available in H13 and H14 grades (@ MPPS). Mini-pleats construction supports scan testing. A lower-temperature sibling of H14CU (350°C), suited to moderate pharmaceutical high-temperature processes. Key features ・Continuous operation up to 250°C ・EN 1822 H13 / H14 compliant (@ MPPS) ・Mini-pleats: high airflow, low pressure drop ・Leak-free, scan-testable Target industries:Pharmaceutical

Features & Specifications

No.ModelEfficiencyW (mm)H (mm)D (mm)Airflow (CMM)Airflow (CMH)Initial PD (Pa)
1H14CH-Z-Q-FS4HR99.995%@MPPS(H14)30561015011.0660270
2H14CH-Z-Q-FS4HR99.995%@MPPS(H14)45745715012.5750270
3H14CH-24-Q-FS4HR99.995%@MPPS(H14)61061015024.01440270
4H14CH-Z-Q-FS4HR99.995%@MPPS(H14)76261015030.51830270
5H13CH-Z-Q-FS4HR99.95%@MPPS(H13)30561015011.0660250
6H13CH-Z-Q-FS4HR99.95%@MPPS(H13)45745715012.5750250
7H13CH-24-Q-FS4HR99.95%@MPPS(H13)61061015024.01440250
8H13CH-24-Q-FS4HR99.95%@MPPS(H13)76261015030.51830250
9H13CH-Z-P-FS4HR99.95%@MPPS(H13)30561029019.01140250
10H13CH-Z-P-FS4HR99.95%@MPPS(H13)45761029025.51530250
11H13CH-35-P-FS4HR99.95%@MPPS(H13)61061029035.02100250
12H13CH-Z-P-FS4HR99.95%@MPPS(H13)76261029044.52670250

Email:sales@baisheng-tech.com

Phone+886-2-25981958

Detailed Description

H14CH/H13CH is the 250°C HEATMOS filter, for pharmaceutical clean zones that do not require the full 350°C specification. Lower cost than the 350°C version while meeting the same EN 1822 standard.

Materials & Construction

PropertySpecification
Filter frameSTAINLESS STEEL
MediaGLASS PAPER
Max. temperature250°C
SeparatorALUMINUM
GasketPTFE / GLASS PAPER
Grille (downstream)-
Grille (upstream)-
SealantSILICONE
Max airflowCan be calculated on request
Max final PD (Pa)500

Airflow vs Pressure Drop (representative)

0100200300400500010002000300040005000Air volume (m³/h)Pressure drop (Pa)H13CH 150mm (Q)H13CH 290mm (P)
H13 representative curves shown. H14 has slightly higher initial PD (~+20 Pa) at the same size.

Applications

- High-temperature clean ovens in pharmaceutical plants - Drying stages of aseptic processing - Cooling zones after biopharmaceutical sterilization

Selection Notes

- **H13 / H14** — select by cleanliness requirement. - **150 mm (Q) / 290 mm (P)** — select by airflow. - For processes requiring >350°C, choose H14CU/H13CU.

Selection References

Before ordering, verify the efficiency grade, media type, and whether the operating environment fits your requirements.